The maximum voltage at the terminals of the dynamo(s) shall not exceed -- volts.

The dynamo(s) shall be of the latest and most efficient pattern; mounted on a base provided with an adjustable belt tightener, so that the belt may be tightened while in operation; capable of operating under full load for consecutive hours without increasing the temperature of any part, especially the armature, fields, and commutator, to such a degree as to endanger the insulation or decrease the efficiency of operation; shall have an insulation resistance of not less than

ohms between all parts insulated from each other; shall be adapted to operate at such speed as will allow the use of high-speed, automatic cut-off engines belted direct; shall be supplied with efficient oiling devices; the armature shall be balanced both electrically and mechanically so that there will be no tendency to spring the shaft, or to draw the armature toward either bearing so as to cause excessive friction and heating, and no vibration; all contacts, brushes, binding posts, etc., shall be so placed and protected that there is the least possible danger of receiving a shock; special attention shall be given to the proper securing of armature conductors to its surface; the dynamo(s) shall be so designed that the power required will be automatically proportioned to the number and the candle power of the lamps burning at any time, and shall be rated with such margin of

safety that

S they
it

41. Foundations.

45. Instruments.

will not be injured if

subjected to a temporary overload of — per
cent. above such rating; if self-exciting, the
coils furnishing the exciting current, and the
commutator shall be so insulated and pro-
tected that it will be impossible under the
ordinary conditions of operation to ground or
cross them on themselves or on the armature
circuit; if separately excited the exciting
dynamo(s) also shall be subject to the general
conditions given above, shall operate at a
potential not exceeding volts, shall be of

ample capacity to excite the fields of
dynamo(s) (each) having a capacity of

c. p. incandescent lamps, and shall operate with no appreciable sparking at the brushes.

(See p. 54, sec. 34.)

(See Note: p. 45, sec. 23.)

,

There shall be provided with each dynamo one ampère meter for indicating the current supplied by the dynamo; one voltmeter or pressure indicator which shall remain constantly in circuit so as to indicate continuously the pressure on the primary mains at the point to which it is connected, and shall be so constructed that the scale is plainly visible at a distance of at least; one insulating baseframe provided with rails and a suitable device for shifting the position of the dynamo

to alter the belt tension; one ground detector which shall continuously indicate the insulation maintained on both sides throughout the system; one pair of efficient lightning arresters; for the field-exciting circuit one hand regulator made entirely of incombustible material, one voltmeter, one brush jig, one double-pole knife switch mounted on an incombustible base, one double-pole fusible cut-out mounted on an incombustible base; if the fields are separately excited there shall be provided with the exciting dynamo one insulating baseframe as above, one endless belt, and also, if it excites the fields of more than one dynamo, one hand regulator for the field circuit of the exciting dynamo, one hand regulator for each of the field circuits of the excited dynamos, and one double-pole knife switch and double-pole fusible cut-out for each of the above field circuits, including that of the exciting dynamo unless lights are operated therefrom, in which case a switch and cut out shall be placed in the main circuit before branching off to the various dynamos.

There shall be provided the following num-46. Converters. bers and sizes of converters:

[blocks in formation]

Each converter shall reduce the voltage on

the primary circuit to

volts on the sec

ondary circuit; shall have its capacity plainly

47. Cables to Switchboard.

48. Starting Plant and Instruction.

49. Renewal Parts.

marked upon it; shall be provided with fuses on both the primary and secondary circuits; and shall be so arranged that when replacing fuses or otherwise working about the converter both the primary and secondary circuits may be opened.

(See p. 56, sec. 36.)

(See p. 46, sec. 25.)

(See p. 47, sec. 26.)

50. Summary.

(See Note: p. 47, sec. 27.)

Each bidder shall fill out completely the following summary:

Number of alternators

Trade number or designation.

Number of exciters

Trade number or designation

Rating of alternators in volts

Rating of alternators in ampères
Rating of exciters in volts

[ocr errors]
[merged small][ocr errors]

Reduction recommended in converters
Make of lamps recommended for use
Dynamo capacity in c. p. lamps of
above make

H. P. required to be delivered at the
pulley at full load with no loss in
the feeders but including exciter.

(See p. 48, sec. 28.)

9744

51. Switch

board.

board Appar

nections.

There shall be placed upon this switch- 52. Switch board, in addition to the dynamo regulating atus and Con apparatus, such switches, cut-outs, and other appliances as are necessary for the proper and convenient manipulation of the circuits, such appliances to be named by each bidder in his proposal.

The appliances and connections shall be such as will permit the operation of any dynamo on any circuit or number of circuits, and the cutting in or out of any dynamo or circuit with certainty and rapidity without in any manner affecting the operation of other dynamos or circuits. They shall also be arranged in such manner as to render it impossible to connect two dynamos together by any arrangement of switches or combination of circuits. (For switchboard connections see secs. 30 and 31, p. 50.)

(See p. 51, sec. 32.)

53. Circuits.

Alternating Current or Direct Current System, with the Parallel System of Distribution.

This contractor shall furnish, and, unless otherwise specified, erect the following apparatus and material:

« НазадПродовжити »