size to accommodate all the regulating appara-
tus, switches, ’bus bars, etc., named below
without crowding, supported on a stout fram-
ing of

and set out not less than from
the wali. A design of the switchboard shall
be submitted with the bid.

ratus.

[ocr errors]

(Note.-This specification includes ouly the 29. Switch

board Appalo instruments used in the simplest of installations. The instruments required for any particular installation must, of course, be determined by its individual purposes and necessities.)

There shall be placed upon this switchboard
all the dynamo regulating apparatus and the
following appliances:

main ampère meters.
ampère meters for risers.
dynamo galvanometers.
dynamo galvanometer switches.
dynamo switches.
s riser)

feeder
switches for connecting system with
dynamos in the building or with external
source of supply.

breakdown switch.

double-pole fusible cut-outs.
(switches, cut-outs, etc., for purely local con-
ditions).

All switches carrying over ampères
shall be knife switches; all other switches
shall have sliding contacts, and shall make

and break contact automatically beyond the control of the operator, who shall simply set the switch at the point of making or breaking

Cut-outs shall be so protected that the molten metal cannot be spattered about on the fusing of the strip.

All switches and cut-outs shall be mounted on incombustible bases.

20. Connections ((oncealed).

All connecting wires shall be carried back of the switchboard using only insulated wire. All joints shall be soldered. All connections to switch t-outs, etc., shall be soldered or made wn approved form of lug or set screw, in all cases care being taken to secure good and sufficient contact to prevent heating and insure permanency; when made with lugs or set screws they shall be in plain sight and easily accessible for tightening. Connecting wires shall be so run and secured that crosses or grounds are impossible in the normal operation of the plant. All main wires shall have a capacity of at least í. M. per ampère, and no wire smaller than --- B. & S. or

B. W. G. shall be used.

31. Connections (sur

face).

All dynamo, 'bus, feeder and riser wires shall be of

S

insulated wire fastened neatly

and securely to the front surface of the switchboard. All bare wires shall be separated from the board by an air space of not

sec

[ocr errors]

less than Bus bars shall be of
tion. All minor connections, such as to pres-
sure indicators, ground detectors, etc., shall
be made on the rear

s
-- insulated wire. All joints shall be sold-
ered. All connections to switches, cut-outs,
etc., shall be soldered or made with an
approved form of lug or set screw, in all cases
care being taken to secure good and sufficient
contact to prevent heating and insure perma-
nency, when made with lugs or set screws
they shall be in plain sight and easily acces-
sible for tightening.' All main wires shall
have a capacity of at least
ampère, and no wire smaller than — B. & S.

- B. W. G. shall be used.

C. M. per

or

The following circuits will centre at the 32. Circuits. switchboard: (Enumeration of circuits

To different floors;
To different sections of the building;
Residence circuits;
Commercial circuits ;
Street lighting circuits;

Power circuits, etc.
This enumeration will largely determine
the extra instruments to be supplied.)

Ss

Incandescent Series System, Dynamos Medium

or High Potential (Variable or Constant),
Current Direct or Alternating.

This contractor shall furnish, and, unless otherwise specified, erect the following apparatus and material:

33. Dynamo(s).

dynamo(s) (each) having a capacity of

c. p., incandescent lamps. The maximum voitage at the terminals of the dynamo(s) shall not exceed volts at full load.

The dynamo(s) shall be of the latest and most efficient pattern; mounted on a base

provided with an adjustable belt tightener, so • that the belt may be tightened while in operation; capable of operating under full load for

I consecutive hours without increasing the temperature of any part, especially the arma

ture, fields, and commutator, to such a degree El Ciput, as to endanger the insulation or decrease the sempio dined efficiency of operation ; shall not spark unduly

with proper care of the commutator and ad-
justment of the brushes, nor under consider-
able variation of load; shall have an insula-
tion resistance of not less than 3. - ohms be-

tween all parts insulated from each other;
the. and sa

sed to working current

[ocr errors]
[ocr errors]

they

shall be adapted to operate at such speed as will allow the use of high-speed, automatic cut-off engines belted direct; shall be provided with efficient oiling devices; the armaiure shall be balanced both electrically and mechanically so that there will be no tendency to spring the shaft, or to draw the armature toward either bearing so as to cause excessive friction and heating, and no vibration; "the dynamo(s) shall be of such design that the power required will be automatically proportioned to the number and candle-power of the lamps burning at any time; if of the direct and constant-current type it shall be so designed that with the proper connections two or more may be operated successfully in series, so that with ordinary care and precaution any dynamo may be added to or taken from the circuit without in any manner affecting the efficient operation of the remainder, and with but a momentary fluctuation in the candle power and steadiness of the lamps; if of the direct-current, constantpotential type they that with the proper connections two or more may be operated successfully in parallel so that with ordinary care and precaution any dynamo may be added to or taken from the circuit without in any manner affecting the operation of the remaining dynamos in circuit or causing any change in the candle

they shall be so designed