Зображення сторінки
PDF
ePub

motion has once been imparted by the handle.

4. Have carrying capacity sufficient to prevent heating above the surrounding atmosphere.

5. Be placed in dry accessible places, and be grouped as far as possible, being mounted, when practicable, upon slate or equally indestructible back boards.

MOTORS.-In wiring for motive power, the same precautions must be taken as with the current of the same volume and potential for lighting. The motor and resistance box must be protected by a double-pole cut-out and controlled by a double-pole switch.

ARC LIGHTS ON Low POTENTIAL CIRCUITS-Must be:

1. Supplied by branch conductors not smaller than No. 12 B. & S. gauge.

2. Connected with main conductors only through double-pole cut-outs.

3. Only furnished with such resistances or regulators as are inclosed in non-combustible material, such resistances being treated as sources of heat.

4. Supplied with globes protected as in the case of arc lights on high potential circuits.

Fixture Work.

1. In all cases where conductors are concealed within or attached to fixtures, the latter must be insulated from the gas pipe system of the building.

2. When wired outside, the conductors must be so secured as not to be cut or abraded by the pressure of the fastenings, or motion. of the fixtures.

3. All conductors for fixture work must have a waterproof insulation that is durable and not easily abraded, and must not in any case be smaller than No. 16 B. & S., No. 18 B. W. G., or No. 3 E. S. G.

4. All burrs or fins must be removed before the conductors are drawn into a fixture.

5. The tendency to condensation within the pipes must be guarded against by sealing the upper end of the fixture.

6. No combination fixture in which the conductors are concealed in a space less than onefourth inch between the inside pipe and the outside casing will be approved.

7. Each fixture must be tested for possible "contacts" between conductors and fixture, and for "short circuits," before the fixture is connected to its supply conductors.

8. The ceiling blocks of fixtures should be made of insulating material.

Electric Gas-Lighting.

Where electric gas-lighting is to be used on the same fixture with the electric light:

1. No part of the gas piping or fixture shall be in electrical connection with the gas-lighting circuit.

2. The wires used with the fixture must have a non-inflammable insulation, or where

concealed between the pipe and shell of the fixture the insulation must be such as is required for fixture wiring for the electric light.

3. The whole installation must test free from "grounds."

4. The two installations must test perfectly free of connection with each other.

Pendants and Sockets.

No portion of the lamp socket exposed to contact with outside objects must be allowed to come into electrical contact with either of the conductors.

CORD PENDANTS-Must be:

1. Made of conductors, each of which is composed of several strands insulated from the other conducior by a mechanical separator of carbonizable material, and both surrounded in damp places with a moisture-proof and a non-inflammable layer.

2. Protected by insulating bushings where the cord enters the socket.

3. So suspended that the entire weight of the socket and lamp will be borne by knots, above the points where the cord comes through the ceiling block or rosette, in order that the strain may be taken from the joints and binding screws. All sockets used for wire or cord pendants should have openings at least equal to one-quarter inch gas pipe size.

4. Allowed to sustain nothing heavier than a four-light cluster, and in such a case sufficient

provision should be made by an extra heavy cord or wire, as a mechanical reinforcement.

5. Equipped with keyless sockets as far as practicable, controlled by wall switches. In no case may a lamp giving more than fifty (50) candle-power be placed in a key socket on a flexible pendant.

CLASS D.-ALTERNATING SYSTEMS.

Converters or Transformers.

CONVERTERS-Must not:

1. Be placed inside of any building except the central station unless as hereinafter provided.

2. Be placed in any but metallic or noncombustible cases.

3. Be attached to the outside walls of buildings, unless separated therefrom by substantial insulating supports.

4. Be placed in any other than a dry and convenient location (which can be secured from opening into the interior of the building such as a vault) when an underground service is used.

5. Be placed without safety fuses at the junction between main and service conductors and safety fuses in the secondary circuits where they will not be affected by the heat of the converter,

Primary Conductors.

In those cases where it may not be possible to exclude the transformers and primary wires entirely from the building, the following precautions must be strictly observed:

1. The transformer must be located at a point as near as possible to that at which the primary wires enter the building.

2. Between these points the conductors must be heavily insulated with a coating of moisture-proof material, and, in addition, must be so covered and protected that mechanical injury to them or contact with them shall be practically impossible.

3. The primary conductors, if within a building, must be furnished with a double pole switch, and also with an automatic double pole cut-out where the wires enter the building, or where they leave the main line, on the pole or in the conduit. These switches should, if possible, be inclosed in secure and fireproof boxes outside the building.

4. The primary conductors, when inside a building, must be kept apart at least 10 inches, and at the same distance from all other conducting bodies.

Secondary Conductors.

The conductors from the secondary coil of the transformer to the lamps or other translating devices must be installed according to the rules for "inside wiring" for "low potential systems."

« НазадПродовжити »