Electric Wiring for the Use of Architects, Underwriters, and the Owners of BuildingsMacmillan and Company, 1896 - 183 стор. |
З цієї книги
Результати 1-5 із 24
Сторінка 51
... protecting their insulating covering from injury , and affording a confined channel through which new wires may , at any time , be drawn . Aside from the accessibility , there is the advantage with METHODS OF WIRING . 51.
... protecting their insulating covering from injury , and affording a confined channel through which new wires may , at any time , be drawn . Aside from the accessibility , there is the advantage with METHODS OF WIRING . 51.
Сторінка 52
... protected from mechanical and chemical injury . A proper conduit will protect the insulation ; it makes possible a more suitable time for running the wires ; it gives compact construction and what may properly be called an elec- trical ...
... protected from mechanical and chemical injury . A proper conduit will protect the insulation ; it makes possible a more suitable time for running the wires ; it gives compact construction and what may properly be called an elec- trical ...
Сторінка 63
... protecting them work only when the full capacity of the system is exceeded . Short circuits or leaks would consequently be more serious in their effects . In a part of the dynamo - room wiring , it is not practicable to have safety ...
... protecting them work only when the full capacity of the system is exceeded . Short circuits or leaks would consequently be more serious in their effects . In a part of the dynamo - room wiring , it is not practicable to have safety ...
Сторінка 74
... protected by a double- pole cut - out and controlled by a double - pole switch , except in cases where one - quarter horse - power or less is used on low - tension circuit , a single - pole switch will be accepted . b . Must be ...
... protected by a double- pole cut - out and controlled by a double - pole switch , except in cases where one - quarter horse - power or less is used on low - tension circuit , a single - pole switch will be accepted . b . Must be ...
Сторінка 76
... protected by the fuse at all . A double - pole cut - out or double- pole switch will , however , cut off all the circuit beyond it , as may be seen by comparing Figures 23 and 24 . or The " switch " is a device that operates ...
... protected by the fuse at all . A double - pole cut - out or double- pole switch will , however , cut off all the circuit beyond it , as may be seen by comparing Figures 23 and 24 . or The " switch " is a device that operates ...
Інші видання - Показати все
Electric Wiring for the Use of Architects, Underwriters, and the Owners of ... Russell Robb Попередній перегляд недоступний - 2016 |
Загальні терміни та фрази
air-space alternating currents ampères approved arc lamp attached batteries become break building burn by-path carbons carrying capacity cause combustible material concealed conductors conduit connection construction copper copper wire cross-connection cuit current passes damp danger devices double-pole ductors dynamo earth elec electric circuit electrical pressure electro-motive force energy excessive current exposed fastened fire fixture floor flow fuse fusible cut-out gas-pipe glass or porcelain globe ground hanger-board heat high-potential incandescent lamps inch inflammable inflammable material Inigo Jones installed insulating covering Insulating-joints leak leakage liable light lightning-arrester low-potential mains melt metal moisture motor multiple system multiple-series necessary neutral wire Ohm's law operated path pipe placed possible potential prevent protected resistance-box rheostat Rule 18 Section series circuit service-switch short circuit shown in Figure socket soldered space switch switch-board temperature tion transformer trical tube underwriters volts W. J. LOFTIE walls waterproof wires leading
Популярні уривки
Сторінка 127 - Definitions). b. Must be placed at every point where a change is made in the size of the wire (unless the cut-out in the larger wire will protect the smaller).
Сторінка 140 - No combination fixture in which the conductors are concealed in a space less than one-fourth inch between the inside pipe and the outside casing, will be approved. h. Each fixture must be tested for "contacts...
Сторінка 64 - Special attention is called to the fact that switchboards should not be built down to the floor, nor up to the ceiling, but a space of at least ten or twelve inches should be left between the floor and the board, and from eighteen to twenty-four inches between the ceiling and the board, in order to prevent fire from communicating from the switchboard to the floor or ceiling and also to prevent the forming of a partially concealed space very...
Сторінка 121 - ... b. Must not be placed in the immediate vicinity of easily ignitible stuff or where exposed to inflammable gases or dust or to flyings of combustible material.
Сторінка 112 - Must be so placed in wet places that an air space will be left between conductors and pipes in crossing, and the former must be run in such a way that they cannot come in contact with the pipe accidentally. Wires should be run over, rather than under, pipes upon which moisture is likely to gather or which, by leaking, might cause trouble on a circuit.
Сторінка 123 - Must not be of such material or construction that the insulation of the conductor will ultimately be injured or destroyed by the elements of the composition. c. Must be first installed as a complete conduit system, without conductors, strings, or anything for the purpose of drawing in the conductors, and the conductors then to be pushed or fished in. The conductors must not be placed in position until all mechanical work on the building has been, as far as possible, completed. d. Must not be so placed...
Сторінка 162 - Must be capable of being disconnected at the power plant, or of being divided into sections, so that in case of fire on the railway route, the current may be shut off from the particular section and not interfere with the work of the firemen. This rule also applies to feeders.
Сторінка 112 - Must be so spliced or joined as to be both mechanically and electrically secure without solder. The joints must then be soldered, to insure preservation, and covered with an insulation equal to that on the conductors.
Сторінка 139 - Must be entirely made of material that will resist the action of illuminating gases and will not give way or soften under the heat of an ordinary gas flame or leak under a moderate pressure.