Electric Wiring for the Use of Architects, Underwriters, and the Owners of BuildingsMacmillan and Company, 1896 - 183 стор. |
З цієї книги
Результати 1-5 із 8
Сторінка 75
... cuts out " any lamp , motor , or other piece of apparatus . The term is , how- ever , becoming commonly ap- plied to fusible cut - outs only . The fusible cut - out ordinarily consists of a block or box of porcelain arranged so that a " ...
... cuts out " any lamp , motor , or other piece of apparatus . The term is , how- ever , becoming commonly ap- plied to fusible cut - outs only . The fusible cut - out ordinarily consists of a block or box of porcelain arranged so that a " ...
Сторінка 76
... fusible cut - out is frequently called a " fuse - block . " A " double - pole " device is one that acts in each of the two poles , two wires , or two sides of a circuit . It is required that cut - outs and switches be double - pole so that ...
... fusible cut - out is frequently called a " fuse - block . " A " double - pole " device is one that acts in each of the two poles , two wires , or two sides of a circuit . It is required that cut - outs and switches be double - pole so that ...
Сторінка 104
... fusible cut - out that will cut off the entire current as near as possible to the entrance to the building and inside the walls . [ Section b . An approved fusible cut - out must comply with the sections of Rules 23 and 24 describing fuses ...
... fusible cut - out that will cut off the entire current as near as possible to the entrance to the building and inside the walls . [ Section b . An approved fusible cut - out must comply with the sections of Rules 23 and 24 describing fuses ...
Сторінка 105
... fusible cut - out required just inside the walls is similar to that required for motors , shown in con- nection with Rule 8 ( a ) . As with motor - circuits , the cut - out is to be double - pole , and it is to be placed as near as ...
... fusible cut - out required just inside the walls is similar to that required for motors , shown in con- nection with Rule 8 ( a ) . As with motor - circuits , the cut - out is to be double - pole , and it is to be placed as near as ...
Сторінка 128
... from this rule in case of large chandeliers . f . All cut - out blocks must be stamped with their maxi- mum safe - carrying capacity in ampères . о FIG . 57. - Fuse Closet . It is required that cut - outs or fuse - blocks be in plain ...
... from this rule in case of large chandeliers . f . All cut - out blocks must be stamped with their maxi- mum safe - carrying capacity in ampères . о FIG . 57. - Fuse Closet . It is required that cut - outs or fuse - blocks be in plain ...
Інші видання - Показати все
Electric Wiring for the Use of Architects, Underwriters, and the Owners of ... Russell Robb Попередній перегляд недоступний - 2016 |
Загальні терміни та фрази
air-space alternating currents ampères approved arc lamp attached batteries become break building burn by-path carbons carrying capacity cause combustible material concealed conductors conduit connection construction copper copper wire cross-connection cuit current passes damp danger devices double-pole ductors dynamo earth elec electric circuit electrical pressure electro-motive force energy excessive current exposed fastened fire fixture floor flow fuse fusible cut-out gas-pipe glass or porcelain globe ground hanger-board heat high-potential incandescent lamps inch inflammable inflammable material Inigo Jones installed insulating covering Insulating-joints leak leakage liable light lightning-arrester low-potential mains melt metal moisture motor multiple system multiple-series necessary neutral wire Ohm's law operated path pipe placed possible potential prevent protected resistance-box rheostat Rule 18 Section series circuit service-switch short circuit shown in Figure socket soldered space switch switch-board temperature tion transformer trical tube underwriters volts W. J. LOFTIE walls waterproof wires leading
Популярні уривки
Сторінка 127 - Definitions). b. Must be placed at every point where a change is made in the size of the wire (unless the cut-out in the larger wire will protect the smaller).
Сторінка 140 - No combination fixture in which the conductors are concealed in a space less than one-fourth inch between the inside pipe and the outside casing, will be approved. h. Each fixture must be tested for "contacts...
Сторінка 64 - Special attention is called to the fact that switchboards should not be built down to the floor, nor up to the ceiling, but a space of at least ten or twelve inches should be left between the floor and the board, and from eighteen to twenty-four inches between the ceiling and the board, in order to prevent fire from communicating from the switchboard to the floor or ceiling and also to prevent the forming of a partially concealed space very...
Сторінка 121 - ... b. Must not be placed in the immediate vicinity of easily ignitible stuff or where exposed to inflammable gases or dust or to flyings of combustible material.
Сторінка 112 - Must be so placed in wet places that an air space will be left between conductors and pipes in crossing, and the former must be run in such a way that they cannot come in contact with the pipe accidentally. Wires should be run over, rather than under, pipes upon which moisture is likely to gather or which, by leaking, might cause trouble on a circuit.
Сторінка 123 - Must not be of such material or construction that the insulation of the conductor will ultimately be injured or destroyed by the elements of the composition. c. Must be first installed as a complete conduit system, without conductors, strings, or anything for the purpose of drawing in the conductors, and the conductors then to be pushed or fished in. The conductors must not be placed in position until all mechanical work on the building has been, as far as possible, completed. d. Must not be so placed...
Сторінка 162 - Must be capable of being disconnected at the power plant, or of being divided into sections, so that in case of fire on the railway route, the current may be shut off from the particular section and not interfere with the work of the firemen. This rule also applies to feeders.
Сторінка 112 - Must be so spliced or joined as to be both mechanically and electrically secure without solder. The joints must then be soldered, to insure preservation, and covered with an insulation equal to that on the conductors.
Сторінка 139 - Must be entirely made of material that will resist the action of illuminating gases and will not give way or soften under the heat of an ordinary gas flame or leak under a moderate pressure.